Axial and Radial fan. Axial
fan can provide large flow at low head. Ex. FD fan, Ignitor fan, ID Fan, etc Radial Fan can provide less quantity at high pressure.
PA fan, Flame scanner cooling air fan, etc
Saturday, 7 December 2013
149.How to control process flow for centrifugal pump and positive displacement pump?
Centrifugal pump - Modulating the discharge side valve.
Positive displacement pump - Modulating recirculation valve.
148.What are the type of pumps and give their typical example?
Positive displacement, reciprocating, centrifugal type, etc. Positive
displacement type - Fuel oil pumps, Reciprocating Type - Chemical dosing pump,
Centrifugal type - Feed water pump and other general service pumps.
147.What are the types of Instrument air compressors? What is loading and unloading?
Reciprocating and centrifugal type. Loading - Compressor running with
suction valve open. Unloading - Compressor running with suction valve closed,
ideal running
146.What are the fail-safe conditions of control valves, give typical example?
Fail safe conditions of Control valves are Fail-Open and Fail-Close
(Depending on the end position reached by control valve on loss of control
signal/air supply).Normally Fail open valves are used in Emergency applications
like recirculation line or Bypass lines (HP bypass, Heater bypass etc). Valves
used for fuel flow are fail close type.
145.What are the characters of Control valve and give example of their application?
The typical flow characteristics of a control valve are Linear, Equal
percentage, Quick opening type.
The characteristic of valve depends of loop sense, differential pressure
across the control valve etc.
Fuel oil flow control - Controller is Linear characteristic. Error at
various valve opening, from 0 to 100%, demands same flow change.The DP across
the control valve is high at loads and decrease with respect to load. Hence
the CV at low loads shall be small compared to at high loads. A Equal
percentage valve will provide such CV. Fuel Oil
Temperature Control - Controller is non linear characteristic. Error is
temperature. Same error at small valve opening require less flow. At higher
valve open demands large flow. The mass of steam required for 50% fuel can only
change the temperature by 50% at 100% fuel flow. DP across the valve is
constant. Hence an Equal % valve can perform better. However the valves characteristics can be matched with the process using adapting gain in DCS using
valve position demand.
144.What is Constant Pressure mode and Sliding Pressure mode?
Large units will be operated at reduced steam pressure at loads less than
60% from 25%. The pressure will be maintained constant at rated value from 60
to 100% load. Typically for a 550 MW Unit, pressure will be 120 bar at 25% load
and increased proportionally to 160 bar up to 60% load. This mode of unit
operation is known as Sliding/Variable pressure mode. The governer valve will remain at a fixed value except for any emergency. From 60% to 100% the pressure
will be maintained constant at 160 bar by modulating the governer valve, it is
called constant pressure mode.In sliding pressure mode an appreciable amount
energy is saved in the BFP.
143.What is Runback?
In a large units, the auxiliaries will be split to two of 2 x 60% capacity.
This will help to produce atleast 50% load during any such auxiliary. Loss
FDF/IDF will reduce air supply. Loss of BFP will reduce feed water supply. Loss
of Mill will reduce fuel supply. When a loss of auxiliary is sensed the load
shall be reduced to below 50% as quickly as possible. Loss of Fan needs
100%/min rate. This control is initiated logically.This is called Runback.
Runback for FDF can be achieved successfully for almost all the boilers.
However the unit can survive for loss of BFP only in the case of assisted
circulation boilers. Loss of coal Mill will transfer the coal flow control to
Manual.The unit will go to Turbine follow Mode for Runback.
142.What is Rundown?
During load ramping, the auxiliaries may not be able to meet the required
load due to change in boiler conditions, aging of auxiliaries, etc. It is
practiced to reduce the load and CMC demand slowly to a safe limit. This is
known as Rundown.
141.What is Load Block?
During CMC mode the demand is applied parallel to BM and TM. The response
of boiler will be slow when compared to turbine. This will create deviation in
boiler loops, such as Fuel flow controller, Air flow controller, Steam
temperature controller, Drum level controller, etc. It is not advisable to
continue load change with a high deviation. The change in load demand will be
blocked until the deviation become less.Load block will be applied for Load
Increase and Load Decrease. Alarm will be initiated to alert the operator.
140.What is Co-ordinate control mode?
In order to get the Optimum response of both Boiler Follow and Turbine
Follow mode, as higher level control function called Co-ordinated Master
Control is designed.In this configuration, CMC will be the main Load demand
controller and will parallely sending demand for fuel from MWD as a feed
forward signal to Boiler Master and the MWD to the Turbine Master in a
Co-ordinate manner. This helps Boiler controls to take corrective measures,
even before the PV is changed and at the same time Turbine control to quickly
respond to load variations utilising the stored energy in the boiler. This mode
is called as MW Control or Co-ordinated Boiler Follow Mode by Vendors.
Sometimes it is necessary to operate plant in Co-ordinated Turbine Follow Mode
( BM - control MW and TM - control steam pressure). This mode helps to over
come the large time lag in boiler.
139.What is Turbine Follow mode?
The Power generation (Load), in a power plant can be changed by changing
the fuel/air demand manually. In this condition the Turbine Master will control
the steam pressure.This Process where in the TG
Master "Follows" Boiler
is known as the "Turbine Follow" mode of operation. During
Turbine Follow Mode, The Boiler Master will be on Manual and Turbine control
will be on Auto (controlling throttle steam pressure)
138.What is Boiler Follow mode?
The Power generation (Load),
in a power plant can be changed by modulating governer valve. This will cause a
change in steam flow in turn a change in steam pressure.The Boiler Master will
change the fuel demand from the SF as FF and by deviation in pressure as feed
back.This Process where in the Boiler Pressure Control "Follows"
Turbine Load controller is known as the "Boiler Follow" mode of
operation. During Boiler Follow mode, Boiler Master will be on Auto
(controlling pressure) and Turbine Master will be on Manual or local Auto
(controlling MW).
137.What is the meaning of MOCS (Multiple Output Control System) and where it shall be applied?
The control system which control single PV using a process PID controller
as Master and an auxiliary Integral controller as slave is called MOCS.When the
PV is controlled by more than 1 final element, using MOCS will provide
automatic gain modification for number of A/M stations on Auto. Also provide
facility to use Feed Forward loop for such loop. One example is the Furnace
Pressure control using 2 x 60% ID Fans. The FF will be from the FD Fan inlet
vane demand.
136.How to compensate the gain for multiple drives for a single process value?
When as single controller is designed to control multiple control elements
in parallel, depending on the number of the control elements in operation, the
controller demand (common) has to be varied for the same process deviation.
This is achieved by dynamically varying
the Controller Gain depending on the number of ouputs active at any given point
of time (Dynamic Gain changer).
135.How to over come the non-linear characteristic of a control’s final element?
If the characteristics of
process variations are linear w.r.t valve opening, but the control valve
characteristics are non-linear, a suitable characterisation curve can be
designed at the ouput of controller to overcome the non-linearity
134.When to use derivative control? When to use dynamic compensation?
Derivative control action is designed when the process variable has a
tendency to change rapidly. Hence an enhanced and immediate control action is
needed with respect to rate of change. It needs careful application as improper
tuning may result in process swinging out of control. Dynamic compensation
action is designed to aid the control action, by the influence of other
parameters (not controller PV), which may recognise the anticipated variation
of controlled PV.The controller response needed may required to be varied under
different conditions and hence typically Feedforward control concepts are used
for dynamic compensation.
133.What is Over-firing and Under-firing? What parameter of the boiler will be affected much? How to overcome?
When load is increased in a boiler, as a dynamic compensation, fuel fired will be more than that required for steady state. This is called over firing. Similarly when load is decreased in a boiler fuel fired will be less than that of steady state. This condition is under firing.
The temperature pick-up in the final super heater will vary considerably. The value of change is proportional to the % of mismatch. The feed forward loop input shall be compensated suitably to over come the effect of mismatch.
132.What is three element control in drum level control? Why it is necessary?
Drum level is controlled using three measurement parameters-- Steam Flow,
Water Flow and Drum level signals. During rapid load changes, the water level
in boiler drum swells or shrinks due to change in Drum pressure. This would
result in erroneous reading in actual Drum level measurements. Hence level
measurement alone will not be adequate for control purposes. In order to
control level effectively, the control loop is designed to vary the water into
drum by balancing the Stem flow (boiler OUT) and Feed water Flow(boiler IN).The
controller signal is corrected thru the actual Drum Level deviations to
continuously correct the steady state level variations.
131.What is generator purging?
During Power generation, Generators radiate enormous heat. Hence the
Generator casing needs to be cooled. Hydrogen gas is used for fillling the
Generator casing as it is most effective. However, H2 will easily react with
air (O2) unless it is >98% pure. In order to ensure that there are no
entrapped air in the Gen casing,the casing is first purged with Nitrogen gas as
N2 is an inert gas.Subsequently, the N2 gas is displaced with H2 and purity
maintained > 98%.
130.What is furnace purge? Why 30% air flow? Why not 100% air flow? Why 5 Min?
Furnace Purge would involve allowing some minimum quantity of air to flow
through the furnace (without fuel) for a specified period of time to remove any
unburnt fuel. This activity is done every time boiler is started by running Air
fans and Draft fans as required. It is expected that with 30% airflow
maintained for a period of 5 min, the volume of air is adequate for the furnace
to be purged completely of all the unburnt fuel that may be residual in the
furnace during the previous firing operations thereby removing possible uncontrolled
ignition/explosion during next firing operation.The Purge cycle is performed
with furnace maintained under the design pressure(draft) conditions.
129.How to confirm the performance of control system?
As a part of Performance Guarantee, C&I contractor is expected to limit the deviations in critical parameters within limits specified (+/- % age) both for steady state and dynamic load variations (Step and Ramp). By proper design of the control system including feed forward/feedback signals and by correct tuning of control loops, the performance of control system is established in limiting the deviations within limits.
128.What is the meaning of load test and what is the use of it in the Control system?
Operation of a plant at
various loads is known as Load tests. The parameters used in Function
generators, which are load dependent are collected after 30 min at each load.
Ex. MW, Steam Flow, Fuel flow, Air flow, O2 in flue gas, SH out temperature,
At outlet temperature, Burner tilt/Gr fan vane position, etc are the
minimum to be collected. Main purpose of the test is to correct all FX as per
the present plant conditions
127.When the gain of a control loop will need to change?
When the response of the Process is different at different conditions (eg:
Oil or Coal or Gas firing, Load increase or decrease, No of Mills in operation,
no of Fans/Pumps in operation etc) the control loop gain needs dynamic
variation design.
126.How to protect the super heater from saturation steam?
By providing Temperature limiting controls to the Setpoint of the Secondary
loop in a Steam Temperature control.
125.When air limit fuel alarm will appear and how to handle it?
During Load demand variations, if the airflow cannot be maintained as per
the fuel demand (refer lead-lag control), the fuel flow will be limited by
actual airflow--air limit fuel alarm. In such a case, the load demand (fuel
flow demand) has to be reduced OR additional air fans(FD) have to be started to
increase air flow. We should also check healthiness of Oxygen analyzer as the
error in its reading can give wrong airflow values for control.
124.Under what circumstances, the boiler master output will hunt and what is the solution?
Boiler Master demand (PV:Bolier outlet pressure) will hunt when the Load
demand controlled by turbine is varying (eg: excessivegrid frequency variation). In such circumstances,
it is better to switch to "Turbine Follow Mode". Boiler controls will
look at Load Variation and Turbine controls will maintain Boiler outlet
pressure.
123.What is balance-less transfer and how to achieve it?
This is experienced in a controller which is controlling more than one
secondary output simultaneously. If one of the secondary o/ps is switched to
manual or fails, the remaining o/ps have to be adjusted(balanced) automatically
to attain the desired parameters. This action of automatic balancing of the
active o/ps (in a multi o/p controller) without experiencing a bump is known as
Balance-less transfer (achieved thru slow ramping). The combination of Auto
Gain change and Tracking techniques are used to achieve the same.
122.What is Bump-less transfer and how to achieve it?
Controllers can be on Cascade/Auto/Manual Modes. Whenever the controller
status is changed, the process should not experience a variation(BUMP). In
order to achieve this, the output should be held in its last value before the
change in status and the output has then to be varied as per the conrol
requirements. Different "Tracking" computations can be configured to
achieve the same(PV-SV track etc.), so that the controller does not see a
deviation during Mode change.
121.How to make sure the failure of transmitter?
Failure of transmitter is determined thru signal out of range (above 106%
(20.96 mA) or below -6%(3.04 mA)) detection of DCS .
120.What will be logic when the transmitter fails?
When both transmitters are healthy, operator can select any transmitter or
average value for control (on Auto).When one transmitter fails, the control
shall changeover to the other healthy transmitter and the alarm (failure)
status to be notified to the operator. When both transmitters are faulty OR
there is a deviation between the two transmitter readings (beyond specified
margin), the control loop shall be forced to Manual and Failure to be alarmed
to operator including forced manual status.Force the controller to
Manual mode, if there is no redundancy
119.What will be operation logic for selection of transmitter when redundant transmitters are used for control?
When both transmitters are healthy, operator can select any transmitter or
average value for control (on Auto).When one transmitter fails, the control
shall changeover to the other healthy transmitter and the alarm (failure)
status to be notified to the operator. When both transmitters are faulty OR
there is a deviation between the two transmitter readings (beyond specified
margin), the control loop shall be forced to Manual and Failure to be alarmed
to operator including forced manual status.
118.How to ensure air rich in the furnace?
The Boiler Master Controller
controls Boiler outlet Steam pressure by regulating Fuel (Coal/Oil/Gas) and Air
required for combustion. For any combustion to be effective , the volume of air
required has to be equal to atleast the Schiometric ratio. However, it is
necessary to prevent Fuel rich conditions in the bolier as it can lead to
unburnt carbon and un-controlled combustion resulting in possible explosion.
Hence, the control system design shall ensure an air rich condition always. to
accomplish the same, whenever there is a demand to increase fuel, the actual
airflow shall be increased first and then fuel flow (Air leads Fuel). When the
Boiler Master demands decrease in fuel flow, first fuel has to be reduced and
then air flow (Air lags Fuel). The Cross limiting circuit ensures the above to
happen--actual Airflow and Fuel flow measurement shall be used to cross limit
increase/decrease (thru Max/Min selectors) to ensure air rich condition always.
117.What is the meaning of lead/lag control with respect to Boiler Master? What is cross limit and cross bias?
The Boiler Master Controller controls Boiler outlet Steam pressure by
regulating Fuel (Coal/Oil/Gas) and Air required for combustion. For any
combustion to be effective , the volume of air required has to be equal to
atleast the Schiometric ratio. However, it is necessary to prevent Fuel rich
conditions in the bolier as it can lead to unburnt carbon and un-controlled
combustion resulting in possible explosion. Hence, the control system design
shall ensure an air rich condition always. to accomplish the same, whenever
there is a demand to increase fuel, the actual airflow shall be increased first
and then fuel flow (Air leads Fuel). When the Boiler Master demands decrease in
fuel flow, first fuel has to be reduced and then air flow (Air lags Fuel). The
Cross limiting circuit ensures the above to happen--actual Airflow and Fuel
flow measurement shall be used to cross limit increase/decrease (thru Max/Min
selectors) to ensure air rich condition always.
116.Why to maintain 6 – 7 Kg/cm2 dp across the feed water control valve
Normally in a boiler the spray water will
be tapped of at the inlet of Feed Water Control valve. At full load the
pressure drop between the tapping point and the attemperator nozzle will be 10
bar without any pressure drop across the FWCV. On minimum auxiliary power
consumption point, this is ideal operating condition. The boiler feed pump
speed will be modulated to provide the quantity of feed water flow to drum.
The 10 bar dp across the spray control
valve is enough to provide the required spray water flow.
At 50% the dp across the spray water
control valve, with same 0 dp across FWCV, will be 2.5 bar. This dp will not be
enough to provide the spray flow. More over the quantity of spray at 50% will
be maximum and that at full load will be minimum.
The required dp across TCV can be provided
by maintaining a minimum dp across the FWCV. Hence in Drum Level control loop,
the feed water flow is controlled by LC and the dp across FWCV is controlled by
the BFP’s speed control.
The steam temperature control is a case
cade loop. The secondary will control after attemperaor temperature. Assume
that spray water required to reduce 1 Deg.C at full load is 1 T/H. The spray
water demand at 50% load to 1 Deg.C.
will be 0.5 T/H. If the dp across the TCV is maintained constant, a Equal %
valve will provide satisfactory results in this application.
If the dp across the FWCV is controlled
constant at 7 bar from 50% to 100%, the dp across TCV will be 9.5 bar at 50% load and at 100% load it will
be 17 bar. In this case an adaptive gain shall be applied .
The dp across TCV can be maintained
constant at 17 bar by setting the FWCV dp at 14.5 bar at 50% and 7 bar at 100%.
115.What are the type of control algorithms used?
Proportional, Integral,
Derivative are the three algorithm of feed-back control
114.What are the reasons for high steam temperature at the primary super heater outlet? How to handle it?
The heat transfer in this zone is purely
by convection. In this the steam flow and mass flow of flue gas shall be
matched. If the flue gas mass is more than the steam flow, the steam
temperature will increase. No attemperator is possible for this section. By
properly adjusting the air flow for this low load will maintain the primary
super heater steam temperature within limits. When the Automatic combustion is
tuned, the fuel/air ratio shall take this into consideration in fixing the excess
air.
113.What will happen if a soot blower is tripped on over current during forward motion?
Normally, if the SB motor trips in the forward position of blower, the
blower can get damaged due to exposure to furnace heat. Hence, either the
blower has to be withdrawn using manual operation from local.
112.What are the parameters to be monitored when they are operated manually?
SB steam pressure and steam temperature, Time cycle and sequence of
blowers.
111.Whether the blowing pressure will be same for all the blowers? How to set the blowing pressure?
The blowing steam pressure for soot
blowers will be different between them. The blowers for final super
heater/re-heater will be maximum. The pressure depends on the temperature
in that zone. Pressure at super heater
zone will be 22 bar, convection super heater zone is 12 bar, economizer zone is
10 bar and it is 8 bar for air heaters.
The soot blower steam will be taken after
primary super heater before attemparator . It will be reduced to 25 bar. Each
soot blower will be provided with a valve. The lift of the valve can be
adjusted by a nut. Hence the pressure after the valve,
the blowing pressure, can be adjusted as
requires. Throttling of the valves shall be avoided if possible.
First the soot blower far away from the
reducing station in super heater zone shall be selected. A pressure gauge shall
be fixed after the valve. The valve shall be left full open. Confirm the
blowing pressure. Adjust the soot blower steam header pressure to get the
blowing pressure of the soot blower.
Move upward towards reducing station and
set the blowing pressure by throttling the valve. The temporary pressure gauge
shall be used for confirmation.
Re-adjust the station if it is to be
increased to get the highest blowing pressure and repeat downward and set the
pressure bu adjusting the lift of the blower valve.
110.What is soot blower? What are the types?
Soot blowers are devices used to blow steam on water walls to remove carbon
deposits/soot. Two types Rotary (Wall blowers) and Long Re-tractable (furnace
walls).
109.The distance between top and bottom tapping in a drum for level measurement using DP transmitter is 1200mm. There are 600 mm apart from center of drum. The normal water level will be 250mm below the center line. The span of the level indicator is plus or minus 250 mm. What will be the calibration range of the dp transmitter?
The minus pressure from Drum minimum level to the constant column vessel
middle is 4 mA.
Ie., minus 1100 mm of WCL – 4
mA
The minus pressure from the drum maximum llevel to the contant column
vessel middle is 20 mA.
Ie. Minus 600 mm WCL – 20 mA.
108.Whether the drum level between the transmitter, direct level gauge and electronic level monitors will be same on load? If no, what is the reason and how the level will be indicating?
The DP transmitter measures the difference of force ( due to pressure +
mass of the liquid/steam) applied at the two ports. When used to measure level,
the same shall be corrected for any change of Density of the liquid in the
legs. When drum level is measured with DP transmitter, the density of water and
steam in one port and the reference coloumn water are applied deriving from
drum pressure. This is a real time correction applied from 0 to rated pressure
of the boiler. Hence the level indicated by the transmitter will be nearer to
the actual in the drum for all load.
However, direct level guages and electronic level monitors (like Hydarstep)
do not provide this correction. The water in the measuring vessel will be less
thatn that of drum. Typically the temperature of the drum will be 340 Deg.C and
the level gauge will be 150 Deg.C. The density of drum water will be 0.6 and
that in the level coloumn will be arround 0.8. This is known sub- cooling. This
will cause a considerable difference in the level between the DP transmitter
and the direct level gauge. It can be 120 mm for a boiler of 180 bar drum
pressure. Mounting/ insulation of measurement legs on which these devices are
mounted will have considerable bearing on measurements of Drum level vis-a-vis
actual level in the drum. The direct mounted devices will read always lower
level compared to compensated DP Transmitter measurement.
107.Whether the drum level between left and right will be same on load? If different what is the reason?
There will some differences between Left and Right side Drum level
measurements primarily due to unbalanced evaporation between side walls. This
is caused by shift in fire ball in a corner fired boiler or unbalance firing of
burners with respect to drum center. It can be to the extend of 50 mm.
106.How to know reverse flow in the case of GR Fan and how to handle it?
A reverse flow of flue gas in the GR
system will produce high temperature at the outlet of GR duct after the fan.
A shut of damper as close as possible at
the inlet to furnace will stop the reverse flow. However during operation of GR
fan a positive feedback from the shaft of fan end will ensure no reverse flow
in the GR system. This is a must when hydraulic coupling or equivalent methods
are used to control the speed of the fan.
105.What is Re-heater? How to control re-heat outlet steam temperature?
In large boilers, to increase the efficiency, the steam from the HP
cylinderr outlet will be taken to the
boiler again and passed through the set of heating coils and used at the MP
cylinder. This heating coil is known as re-heater.
In a wall fired boiler the flue gas from Eco-inlet will be pumped through a
fan to the furnace. This is known as gas re-circulation. This way the flue gas
mass will be more than the steam flow. This will help to increase the
temperature pickup in the re-heater. In this case the re-heater pickup may be
mainly by convection.
Some times flue gas will be bypassed over the re-heater.
In a corner fired boiler, burners will be tilted up or down to control
re-heat temperature. In this case the Effective Projected Radiant Surface
(EPRS) of the re-heater is changed. In this type of arrangement, re-heater
coils are in such a way that the effective heat pickup is by radiation.
Two methods are in practice: Reheat Spray control, Burner tilt/Bypass damper/Gas re-circulation control systems.
Two methods are in practice: Reheat Spray control, Burner tilt/Bypass damper/Gas re-circulation control systems.
104.Assume that there is a load reduction in the Unit. The control system has changed to manual. How you will control, Boiler Master, Drum Level and Steam Temperature control?
Boiler Master
Check/adjust Boiler Master demand proportional to the steam flow.
Drum Level
Check/adjust Feed water flow nearest to the steam flow.
Steam Temperature
Check/adjust super heater inlet temp nearest to that corresponds to steam flow.
Check/adjust Boiler Master demand proportional to the steam flow.
Drum Level
Check/adjust Feed water flow nearest to the steam flow.
Steam Temperature
Check/adjust super heater inlet temp nearest to that corresponds to steam flow.
103.What are the control final elements used?
Control Valves (pnuematic, Hydraulic and electric actuator), Power
cylinders, Variable speed controllers are the main final control elements used.
102.What are the feedwater heaters in the system and what is their function?
Feedwater heaters are nothing but heat exchangers between BFP and Boiler
drum. These heaters will impart heat to feed water to prevent large temp
differential between water in boiler drum and the in-cpminf feedwater. Large temp
difference would result in water hammering. these heatersoving efficiecy of
overall thermal cycle.
101.What is the function of De-aerator? What is the operating pressure?
De-aerator helps in removing dissolved O2 in the condensate thereby
preventing possible corrosion inside the pipelines. Normally it is maintained
at Positive pressure sufficient to maintain NPSH for BFP at all loads.
Normally, for 210 Mw plant,the Dearator will be maintained at 1.5--3.5 bars.
100.What is the condensate pump? What is the critical point of NPSH for the pump and how to handle it?
Condensate pumps help circulate water (condensate) from Condenser thru LP
heaters to De-aerator. Net Positive Suction Head (NPSH) is the minimum Head
(pressure) required at the suction of the Pump to function properly. The NPSH
can be maintained by a combination of the Pressure and the Level at the vessel
from which the pump is taking its suction from.
99.What is the function of cooling water? How many types of cooling systems are there?
A circulating water system at atmospheric
temperature is used to remove exhaust medium temperature is Cooling water
system.
Condenser cooling water system and
Auxiliary Cooling water system are the 2 main cooling water systems in use in a
power plant.
Condenser cooling water system is a once
through system when sea water is used for cooling. This is the most common
practice in the world. However river water with cooling towers are also used in
inland plants. Natural cooling tower and
forced cooling tower are two types.
Bearing lub oil, Turbine operating oil,
lub oil, etc are cooled in a tubular heat exchangers using a closed circuit
cooling water system. This cooling water is mostly raw water used for water
treatment plant.
98.What is the function of condenser?
Condensers are used to remove Heat from Steam and thereby convert steam
into water. Normally this is at the steam exit of Turbine.
97.What is the function of Air-ejector? How many types are there?
Normally Ejectors are used for
creation of vacuum in a vessel. There are two types--Air ejectors and Steam
ejectors.
96.How to control NOx emission?
Keeping the flame temperature less than 950
Deg.C will reduce the NOX emmission. The achieve the above condition the O2 in
the air can be reduced to 18% by adding flue gas from economizer outlet in the
wind-box. Alternately air can be admitted at the top of the flame.
95.How to reduce SOx emission?
By using fuel with lower sulphur content and also by installing
de-sulphurisation plants to remove sulphur from flue gas at chimney.
94.What are the chemical parameters shall be monitored at the chimney exit?
CO, CO2, SOx, NOx, dust burden & smoke density.
93.What is the function of Chimney and its principle?
The main function of chimney
is to dispose the flue gas at a high level so as spread it to a wide area and
thereby reducing the pollution.
92.What is the Smoke Density and what is its regulation limits and operation limits?
Flue gas consists of large quantity of CO
is smoke. When light can pass through the flue gas fully, the smoke density is
0%. When no light pass through the flue gas, smoke density is 100%.
Smoke emission of 20% in the chimney is
allowed. However a good practice is to operate a boiler within 0 to 5% smoke
density in the flue gas.
Operation of a boiler at more than 40% for
more than 5 min in a day is an offense and subject to penalty by Government.
91.Explain the principle of EP and their components? What may the reason for low current and High voltage and High current and Low voltage? How to set the operating condition manually?
Two
Electrodes at high potential difference of DC supply will be build in the flue
gas path after air heater before ID fan. The emitting electrode is a thin wire.
The potential strength around wire will ionize the gas. This is known as Corona . The ionized gas
will be with Electrons and positive ions. The collecting electrode are plates
and provide large area.
The
electrons are traveling from discharge electrode towards the collecting
electrode at a high velocity. ( Normally the gap is 250 mm).The flue gas
consists of dust is passing through the electrode at a low velocity of 1 m/sec
or less. The dust particles are bombarded by
the electrons and attached to the dust. The dust will be now charge
–vely. They are attracted by collecting electrode plates. The velocity at which
the dust is moving towards collectors is known as migration velocity.
Migrations
velocity will be more than the gas velocity.
This bring the dust to the collectors. There they are attached to the
plates. The efficiency of a zone of ESP will be around 90%.
Discharge
electrodes, collecting electrodes, Insulators, high voltage
transformer/rectifiers, hammering systems for the electrodes and controllers are some of the main components
of an ESP.
Low
current and High voltage is caused by the deposit of fine dust on discharge
electrode.
High
current and low voltage is caused by deposit of coarse dust on the collecting
plates. High resistive dust will make the condition worst in this case. There
will be corona near collecting plated when high potential strength is
established by the dust deposit. This phenomenon is called Back Carona. The
electrons from this corona will combine with the positive ion from the main
corona and similarly the positive ion from back corona will combine easily with
electrons from main corona. The dust will escape from ESP to chimney.
When
control is on Manual, increase the current until there is spark. Leave at a
level where 2 to 5 sparks/min is occurring.
90.What is the function of dust collectors and what are the types of dust collectors are there? What are the limits of the precipitators? What is the environment limits?
Ash and unburned carbon will leave the
furnace along with flue gas. These dusts shall not be left to chimney. To
control pollution in the atmosphere, the dust shall be collected by some means
before going to chimney. The equipment serves this function is dust collectors.
Mechanical separators, Electro static
precipitator and bag filters are some of the dust collectors used commercially
in boilers.
The finesse is the limit in the case of
mechanical separators .
Electrical resistance is the limit for ESP
40 mg/M3 of dust burden is accepted in
many countries. However dust burden specified is 20 mg/M3.
89.What are the main parameters shall be controlled during start-up of turbine?
Pressure and Temperature are the steam
parameters to be matched with turbine metal temperature.
88.What is the function of Circuit Breakers and what are the types and their applications?
A device used to close/Open a electrical
equipment to the power supply is called
Circuit Breaker.
They are named by the cooling or arc
quenching media used in the device. When an equipment is disconnected from a
power supply, the potential strength will be more. This will produce heat in
between the surfaces and cause the media to ionize. This is spark. If the spark
continues and it will be called as Arc.
The heat energy will damage the device.
To reduce the effect of heat generation,
the area provided to the breaker will be
increased. The time to separate the equipment from power supply will be
minimized by using spring. However the arc can be controlled by cooling or
using media which can withstand high potential strength.
87.How to test and maintain Battery?
By periodically measuring End cell voltage and the density of Acid to be within limits. Acid
Topping up is needed if density goes low.Nowadays, Maintenance free batteries
are available, whose life is 10--15 years.
86.What is UPS and what is its function and what are their components?
UPS is Un-interruptable Power Supply System. The main componenets are
Charger, Inverter and Battery bank. Normally,these are used to provide power
supply for limited period to Control and Instrumentation systems during Main AC
power failure.
85.What is Jacking oil pump?
A separate high pressure oil pumping system is designed to facilitate
Baring operation and the Pump is known as Jacking oil pump. This pump is
switched on both at the the beginning of Baring operation.
84.What is baring gear?
Normally, the TG rotor is a heavy mass and rests on the bearings, when no
steam is admitted to Turbine. In order to prevent metal to metal
contact/erosion during initial steam admission, the rotor mass is lifted
(Jacked up) slightly away from bearing metal thru thin film of high pressure
Oil.Baring Gear is the motive force to Rotate the TG rotor in slow speed. This
is needed to faciliate easy rotation of TG on steam admission. The TG rotor is also
put on barring on Turbine stop to assist in uniform cooling of rotor mass until
the turbine metal reaches the room temperature.
83.What is the function of Exciter and how many types of exciters are there?
Exciter is the device which is providing
the supply to provide field current of a generator.
Mechanical with a normal DC generator
Static Exciter – Provide necessary supply
from the AC supply by rectifying by using Thyristors.
82.What is the function of AVR and AQR? How to maintain the export power factor?
AVR – To maintain the terminal voltage of
a Generator
AQR – To maintain the Power Factor
Using Unit Transformer tap change in
conjunction with AQR, the power factor of the export power factor can be
maintained.
81.What is synchronizing? How to synchronize?
Connecting an incoming power supply to the
grid or existing system is Synchronizing.
Frequency, phase angle and magnitude of
voltage shall be same for both incoming and running power supply. Normally an
indicating instrument will be provided to compare them. When they are satisfied
the meter will be at 12 O’clock position. The breaker shall be closed at this
condition.
80.How many types of over speed trips are available for turbine and what are the setting?
Electrical Over speed protection
Mechanical Over speed protection
Trip setting for Electrical is 1.05 times
the rated speed and that of Mechanical is 1.1 times the rated speed.
A PID speed control will be provided as
over-ride to the load control. A Troop control also will be provided with 0.25
Hz dead band. The normal troop setting will be 4 to 8% . The range will be upto
20%.
Troop control is a proportional control.
Example 4% troop will produce a 100% output with a deviation 2 Hz. Assume a
Unit is running at full load with GOV demand as 95%. The GOV demand will be 0
at 51.9 Hz.
In addition to avoid a turbine tripping
due to over speed, Anticipatory Load Schedule logic will be provided. In such
case during a load reduction more than 25%, the electrical and thermal load
will be compared and if thermal load high after 2 sec, the GOV will be demanded
to close fully for a few second and release to the position required by the
electrical load before closing.
79.How to check the Generator and Unit Transformers?
Generator is tested by the above test.
Unit Transformer
- Oil centrifuging
- Open Circuit Test
- Short Circuit Test
Unit transformer is checked by back
charging. However some companies will nto agree for back charging. They are
tested using Generator by slowly increasing voltage.
78.What are the pre-commissioning activities of Generator?
- Excitation
- Open Circuit Test
- Short Circuit Test
- Synchronizing
77.What are the pre-commissioning activities of a steam turbine
- Steam blowing of pipes
- Oil flushing
- Vacuum test
- Initial rolling
- Trial rolling
76.What is SCAH? And how many types of them in the market?
As explained above the air will be
pre-heated before admitting to rotary air heater using steam. This heat
exchanger is known as Steam Coil Air Heater (SCAH).
Coil type and vertical tube are the two
types used in the market. Coil type is using simple instruments and control.
But efficiency is low. The Trap used at the outlet of steam can only extract
the latent heat from the steam. The steam pressure will be 10 to 14 bar. The
exit temperature will be around 200 Deg.C.
In a vertical tubular type the water is maintained in the tubes and the
heat can be extracted as low as 70 to 100 Deg.C.
75.What is the need for an Airheater? How many types are there? What is cold end corrosion? How to protect from cold end corrosion?
If the heat input from fuel is extracted
as much as possible, the efficiency of the boiler will increase. The flue gas
temperature at the outlet of economizer is around 300 Deg.C. The process media,
which is less than 300 Deg.C., is air used for combustion. The heat ex changer used to extract the heat from flue gas after economizer to air is called Air
heater.
Two types are in the market. One is
Tubular and the other one is Rotary air heater. Tubular air heater is used in
small boilers. Rotary air heaters are used in large size boilers above 110 MW.
The average temperature between the exist
flue gas and entering air is the temperature at the exit of air heater. This end
is called cold end.
If the cold end temperature goes below
sulphur dew point, suphuric acid will form on the metal. This will cause
corrosion of the metal. The metal shall be protected from this possible
corrosion.
One method is using non metallic material
at the cold end. Rotten iron and Ceramic are used in rotary air heaters.
Another method is to keep the cold end temperature higher than sulphur dew
point. For this purpose, the air will be pre-heated by steam before admitting
to rotary air heater. Both of them are practiced in majority cases.
74.What is economizer? How to protect the economizer from evaporation?
To increase the boiler efficiency, the
feed water is heated further using flue gas. This section of heat recovery
coils are known as Economizers.
Main criteria are that the steaming shall
be avoided for smooth flow of feed water in to drum. Otherwise hammering will
take place in the feeder tubes.
The flue gas temperature at the exit of
economizers shall be maintained well above Sulphur dew point for the fuel in use.
A feeder pipe with non return valve and an
isolating valve (for maintenance) will be connected at the bottom header of the
economizer. This keep the water level in the economizer will be same as that of
drum when there is no feeding from boiler feed pump. This will avoid
evaporation in the economizer.
73.What is super heater and how many types are there?
Additional heat is added by increasing the
steam temperature through bundle of tubes.
These are Super heaters.
There are two kind of super heaters used
in a boiler. Convection types are placed in the second pass and heat transfer
will be from flue gas by convection.
The exit coils will be placed at the top
of furnace. Heat transfer will be mainly by Radiation. This is the Final super
heaters.
When the tubes are staggered horizontally,
between the two headers, they can be provided with drains. This is known as
drainable super heaters. This arrangement is practiced in oil/gas fired
boilers. In a coal fired boiler, they are placed vertically and known as Platen
super heaters. The condensate in the bottom of each coil shall be made to
evaporate to allow passage for steam. This is achieved by slow firing with vent
open. The starting time will be more in this case before closing vents.
72.What is steam separators and how many types will be there in a drum?
The steam from the raiser tubes will be
mixture of steam and water particles. This is known as wet steam. Steam shall
be separated from water particles. The devices used are called steam
separators.
This functions are done in the drum. The
steam from raisers ate taken back to drum and there it is made to pass through
the separators.
Centrifugal type of buckets of many in
number will be provided. This is Primary separators. The steam will be passed
through radiator kind of separators before leaving the drum at the top. This is
known as Secondary separators.
71.What is the function of Bucks- stay in a boiler?
The furnace will expand in
all the 3 axis. To keep the shape it will be fixed at the middle of each side
by a strong beams and moving connections will be provided at the corners. This
frame or structure is called Bucks-stay
70.How many place the expansion will be checked?
Drum, in the furnace at least 3 places,
burner area and at the end.
69.What is the boiler expansion? How much will be the expansion of a boiler at burner level?
Boilers will expand when subject to
heating. To allow the expansion, they will be either supported from top by
hanging or from bottom.
As a thumb rule, for every 100 Deg.C. per
meter, the expansion from fixed support, will be 1.5 mm.
A 800 T/H capacity boiler, will expand to
a maximum at the end will be 150 mm.
68.What is electrical relief valve and how to set up?
Electrical relief
valve is used in M.S line to relieve the
excess pressure,
thereby
reduce the frequency of lifting the M.S
line S.H safety valve.
The ERV is set
for lifting electrically
(by solenoid ) to operate below
the
set pressure of super heater safety valve.
67.How to set a safety valve? What is Lift and Blow down? How to adjust them?
Raise boiler
steam pressure. Near set pressure, lift the stem manually by using rope on the
hand pop level. Increase pressure and confirm that the valve is opening at the
required set value. Start from the highest set pressure valve. Jack close the
low set pressure valves.
Confirm blow
down. It shall be between 2 to 5%.
Lift : The amount
of raise
of stem while lifting is called “lift”.
Blow down : The difference between set pressure & reseat pressure
Expressed in Æ
percentage of set pressure.
Adjustment :
Lower ring adj :- To set a clear
popping, to close slowly. (To avoid
Simmering & chattering ).
To reduce simmer, move the lower ring upward
ie. Anticlockwise direction.
1 notch =
42.2ksc.
Upper ring adj. :- To adjust blow down .
To reduce
blow down, move the upper ring upward,
ie.,
turn anticlockwise.
To
increase blow down , move the ring
downward66.How many safety valves shall be provided for a boiler and where?
The following are the main safety valves typically in a boiler :
Boiler drum (L) - 2 nos
Boiler
drum (R) - 1 no
Super heater outlet (R) - 1 no
Reheater
Inlet (L) - 1 no
Reheater Outlet (R) - 2 nos
Reheater Outlet (L) - 1 no
Super heater Outlet (L) -
2 nos
65.What is safety valve and Relief valve?
A valve provided on any pressure vessel
which will open to release the pressurizing media when the pressure exceeds the
set value.
Safety valve will open at a preset value
and sit again at a fixed reset pressure.
Relief valve also will open at set value
and sit when the pressure is less than set value.
64.What is steam blowing? Why it is necessary? How many type of steam blowing are in the practice? What is deciding factor for the completion of steam blowing and who shall decide the completion?
A process undertaken during initial plant installation, to remove any mill
scale in SH tubes and pipes by blowing steam and venting out the same is known
as steam blowing. Continuous and Puff Steam blow methods are used. In
continuous method the boiler shall be prepared for full load and the steam at
full load flow, pressure and temperature shall be blown for some hours. In
Puffing method, pressure in the boiler will be raised to 250 Deg.C, at around
40 bar, and the stop valve in the temporary pipe is opened quickly. This will
create a sudden change in velocity in the pipe. It is claimed that this the
best economical method. A target steel plate is put at the end of the pipeline
sections and the same is observed for the indentations after the steam blow to
establish the cleanliness of the steam pipes. Since the steam admitted to
turbine should not contain any contaminant (damages the turbine internals), the
Turbine commissioning in-charge will give clearance for the completion of
satisfactory steam blowing operation.
63.What is the procedure for Alkali-boilout, Acid cleaning, passivation, etc.?
Alkali boil out - It uses Alkali such as NAOH, CACO3, etc. The purpose is
to remove grease in the tubes. The boiler will be pressurized to 20 Kg/cm2 and
kept for 24 to 48 hours. Blow-down will be opened for 1 min for every 1 hour.
End point is no traces of grease in the effluent.
Acid Cleaning – It uses diluted Sulphuric acid. The purpose is to remove
loose mill scales in the boiler tubes. The end point is the saturation of iron
in the mixture or 2 hours, which one is early. Sometime acid cleaning at very
mild concentration will be applied for old boiler to remove any scaling in the
water wall tubes.
Passivation – The reaction of acid shall be cleared after acid cleaning.
For this purpose, the mixture Ammonia phosphate at 200 ppm and Hydrazine at 200
ppm will be left to evaporate at 20 Kg/cm2 for 24 hours.
The effectiveness will be confirmed by the colour
on the coating tube inside.All chemical cleaning are applied for water wall tubes. SH shall be protected during Acid cleaning
62.What are the chemical cleanings for a boiler and end point for them?
Alkali boil out - It uses Alkali such as NAOH, CACO3, etc. The purpose is
to remove grease in the tubes. The boiler will be pressurized to 20 Kg/cm2 and
kept for 24 to 48 hours. Blow-down will be opened for 1 min for every 1 hour.
End point is no traces of grease in the effluent.
Acid Cleaning – It uses diluted Sulphuric acid. The purpose is to remove
loose mill scales in the boiler tubes. The end point is the saturation of iron
in the mixture or 2 hours, which one is early. Sometime acid cleaning at very
mild concentration will be applied for old boiler to remove any scaling in the
water wall tubes.
Passivation – The reaction of acid shall be cleared after acid cleaning.
For this purpose, the mixture Ammonia phosphate at 200 ppm and Hydrazine at 200
ppm will be left to evaporate at 20 Kg/cm2 for 24 hours.
The effectiveness will be confirmed by the colour on the coating tube
inside.
All chemical cleaning are applied for water wall tubes. SH shall be protected during Acid cleaning.
All chemical cleaning are applied for water wall tubes. SH shall be protected during Acid cleaning.
61.Can it be possible to open the inlet vane of an IDF during trial run and why?
It may not be possible. The fan may be over loaded. A fan handle volume.
When the inlet vane is fully open, the volume of gas/air will be the maximum.
ID Fan handles flue gas at 120 to 140 Deg.C. The density of gas will be less
compared to air
( Air density - 1.29 Kg/M3 at 15 Deg.C) . The load of motor is
proportion to mass of the gas. Hence the motor may over loaded. Care shall be
taken during trial run of ID Fan. The inlet vane shall be opened to the rated
current.
60.How to operate the SADs in a wall fired and corner fired boiler?
SADs will be opened fully in
wall fired boiler. The air flow to each burner in service will be always equal.
Hence unbalanced loading of fuel between mills shall be avoided except
starting. In a corner firing, the fuel air damper will be function of mill
load. The AAd will maintain the Wind-box/furnace differential pressure constant
at 40 mm WCL before any mill is in service and at 180 mmWCL after any mill is
taken to service
59.What are the Secondary Air Dampers and how they differ between wall fired and corner fired boilers?
The damper controlling the combustion air to fuel at the burner is known as
Secondary air. The air which is used to transport fuel to the burner is Primary
air. Normally secondary air will be admitted very close to the fuel. In a wall
fired boiler the secondary air will be spinned around the fuel spary. If the
secondary air axial velocity component is greater than flame propagation velocity, then the flame will become unstable. Hence the excess air will be
supplied at the outer circle. This air is known as Tertiary air. In a corner
fired boiler, the secondary air is known as Fuel air, the damper is called FAD.
The air will be admitted axially at the bottom and top of the fuel nozzle and
will rotate at the peripheral of the fire ball. The excess air will be admitted
at he next level of each FAD outlet and
called Auxiliary air and damper is called AAD.
58.How to categorize the type of boilers?
a) According to the use – Utility
Boiler, Processing type Boiler.
b) According to the tube content
- Fire tube , Water tube Boilers.
c) According to the furnace position
– Externally fired & Internally fired boiler.
d) According to the circulation -
Natural
57.What is the Gasket of valves? Name the type of bonnet gaskets and gland gaskets for valves?
The soft material used between the body and the bonnet of a valve is called
gaskets.Asbestos reinforced Paper, rubber, metallic gaskets (Spiraket gaskets),
etc.
56.What is mechanical seal?
For any pump, there will be glands between the rotor and the body at the
end before bearing. This is to avoid leak along the shaft. In a high pressure
pumps, instead of asbestos gland ropes, a self lubricating material made of
carbon and iron will be used. This is called Mechanical seal.
55.Explain the procedure of alignment of a rotating equipment? What is reverse and soft foot alignment?
Two rotating shaft shall be aligned such that the shear forces and bending
moments at the coupling are zero.
Final alignment of rotors are obtained by
adjusting the bearings ( for turbine rotors) and by adjusting the motor for
Pumps, fans, etc to give parallelism and concentricity at each pair of
couplings.
The alignment is carried out by measuring
the face gaps and periphery errors between couplings.
Gap measurements, using suitable gauges,
are taken at the top, bottom and two side positions and a repeat set taken with
both shafts rotated through 180 deg. The average of the two sets indicates the
true parallelism of the coupling faces, eliminating any errors due to out of
truth between couplings and shaft.
Concentricity is checked by measuring
between the peripheries of the two couplings, using either dial indicators or
feeler gauges, to a finger attached to one of the coupling. To eliminate
coupling errors, both shafts are turned together and readings taken at the top,
bottom and two side positions.
Calculations using ratios and similar
triangles, taking account of shaft length, distance between bearings and
coupling diameter, determine the adjustment required at the bearings to obtain
shaft alignment.
With solidly –coupled shafts, it is usual
to work to very close tolerances of the order of plus/minus 0.025 mm.
54.Explain the balance drum of a BFP?
Normally the differential pressure between discharge and suction sides of
Boiler Feed Pumps are quite high. Due to this, the rotor section experiences
very high trust in one direction. The movement of rotor (Axial shift), if it
exceeds manufacturer's tolerances, will result in rubbing of mechanical seals
and damage the same. A Balance Drum is created by interconnecting suction and
discharge sides suitably and the wear out of seals can be inferred by measuring
Balance drum pressure.
53.What are the trip commands for a pump?
Typical Trip interlocks for Pumps are: Bearing Temp OR Vibration High,Lube
oil press Low, Suction valve Closed , Electrical switch gear faults.
52. What are the trip commands for a Fan?
Typical Trip interlocks for fans are: Bearing Temp OR Vibration High,Lube
oil press Low, Electrical
switchgear faults.
51.What is partial loss of flame?
In a wall fired boiler when a flame
scanner sense no flame, the respective burner shut-off valves are demanded to
close. If they are failed to close after 10 sec. it is announced as Partial
Flame loss.
If the number burners are less than a
number which can cause unsafe condition, MFT will be initiated. Sometimes a
load factor less then 75% is also ANDed for MFT.
Conservatively some plants are initiating
MFT for Partial Flame loss irrespective of any condition of the boiler.
Subscribe to:
Posts (Atom)