120.What will be logic when the transmitter fails?

When both transmitters are healthy, operator can select any transmitter or average value for control (on Auto).When one transmitter fails, the control shall changeover to the other healthy transmitter and the alarm (failure) status to be notified to the operator. When both transmitters are faulty OR there is a deviation between the two transmitter readings (beyond specified margin), the control loop shall be forced to Manual and Failure to be alarmed to operator including forced manual status.Force the controller to Manual mode, if there is no redundancy