The blowing steam pressure for soot
blowers will be different between them. The blowers for final super
heater/re-heater will be maximum. The pressure depends on the temperature
in that zone. Pressure at super heater
zone will be 22 bar, convection super heater zone is 12 bar, economizer zone is
10 bar and it is 8 bar for air heaters.
The soot blower steam will be taken after
primary super heater before attemparator . It will be reduced to 25 bar. Each
soot blower will be provided with a valve. The lift of the valve can be
adjusted by a nut. Hence the pressure after the valve,
the blowing pressure, can be adjusted as
requires. Throttling of the valves shall be avoided if possible.
First the soot blower far away from the
reducing station in super heater zone shall be selected. A pressure gauge shall
be fixed after the valve. The valve shall be left full open. Confirm the
blowing pressure. Adjust the soot blower steam header pressure to get the
blowing pressure of the soot blower.
Move upward towards reducing station and
set the blowing pressure by throttling the valve. The temporary pressure gauge
shall be used for confirmation.
Re-adjust the station if it is to be
increased to get the highest blowing pressure and repeat downward and set the
pressure bu adjusting the lift of the blower valve.