If the heat input from fuel is extracted
as much as possible, the efficiency of the boiler will increase. The flue gas
temperature at the outlet of economizer is around 300 Deg.C. The process media,
which is less than 300 Deg.C., is air used for combustion. The heat ex changer used to extract the heat from flue gas after economizer to air is called Air
heater.
Two types are in the market. One is
Tubular and the other one is Rotary air heater. Tubular air heater is used in
small boilers. Rotary air heaters are used in large size boilers above 110 MW.
The average temperature between the exist
flue gas and entering air is the temperature at the exit of air heater. This end
is called cold end.
If the cold end temperature goes below
sulphur dew point, suphuric acid will form on the metal. This will cause
corrosion of the metal. The metal shall be protected from this possible
corrosion.
One method is using non metallic material
at the cold end. Rotten iron and Ceramic are used in rotary air heaters.
Another method is to keep the cold end temperature higher than sulphur dew
point. For this purpose, the air will be pre-heated by steam before admitting
to rotary air heater. Both of them are practiced in majority cases.