Electrical Over speed protection
Mechanical Over speed protection
Trip setting for Electrical is 1.05 times
the rated speed and that of Mechanical is 1.1 times the rated speed.
A PID speed control will be provided as
over-ride to the load control. A Troop control also will be provided with 0.25
Hz dead band. The normal troop setting will be 4 to 8% . The range will be upto
20%.
Troop control is a proportional control.
Example 4% troop will produce a 100% output with a deviation 2 Hz. Assume a
Unit is running at full load with GOV demand as 95%. The GOV demand will be 0
at 51.9 Hz.
In addition to avoid a turbine tripping
due to over speed, Anticipatory Load Schedule logic will be provided. In such
case during a load reduction more than 25%, the electrical and thermal load
will be compared and if thermal load high after 2 sec, the GOV will be demanded
to close fully for a few second and release to the position required by the
electrical load before closing.