Reciprocating and centrifugal type. Loading - Compressor running with
suction valve open. Unloading - Compressor running with suction valve closed,
ideal running
Saturday, 7 December 2013
146.What are the fail-safe conditions of control valves, give typical example?
Fail safe conditions of Control valves are Fail-Open and Fail-Close
(Depending on the end position reached by control valve on loss of control
signal/air supply).Normally Fail open valves are used in Emergency applications
like recirculation line or Bypass lines (HP bypass, Heater bypass etc). Valves
used for fuel flow are fail close type.
145.What are the characters of Control valve and give example of their application?
The typical flow characteristics of a control valve are Linear, Equal
percentage, Quick opening type.
The characteristic of valve depends of loop sense, differential pressure
across the control valve etc.
Fuel oil flow control - Controller is Linear characteristic. Error at
various valve opening, from 0 to 100%, demands same flow change.The DP across
the control valve is high at loads and decrease with respect to load. Hence
the CV at low loads shall be small compared to at high loads. A Equal
percentage valve will provide such CV. Fuel Oil
Temperature Control - Controller is non linear characteristic. Error is
temperature. Same error at small valve opening require less flow. At higher
valve open demands large flow. The mass of steam required for 50% fuel can only
change the temperature by 50% at 100% fuel flow. DP across the valve is
constant. Hence an Equal % valve can perform better. However the valves characteristics can be matched with the process using adapting gain in DCS using
valve position demand.
144.What is Constant Pressure mode and Sliding Pressure mode?
Large units will be operated at reduced steam pressure at loads less than
60% from 25%. The pressure will be maintained constant at rated value from 60
to 100% load. Typically for a 550 MW Unit, pressure will be 120 bar at 25% load
and increased proportionally to 160 bar up to 60% load. This mode of unit
operation is known as Sliding/Variable pressure mode. The governer valve will remain at a fixed value except for any emergency. From 60% to 100% the pressure
will be maintained constant at 160 bar by modulating the governer valve, it is
called constant pressure mode.In sliding pressure mode an appreciable amount
energy is saved in the BFP.